Chapter Three Operation
Page 45 © April 2007
3.12.3 Modbus TCP to RTU Server
The Modbus TCP to RTU Server allows an Ethernet Modbus/TCP Client (Master) to
communicate with a serial Modbus RTU Slave. The 805U-E makes this possible by
internally performing the necessary protocol conversion. The conversion is always performed
by the 805U-E which is directly connected to the Modbus serial device (i.e. only this module
needs to have Modbus TCP to RTU Server enabled).
The above example demonstrates how a Modbus/TCP Client (Master) can connect to one or
more Modbus RTU (i.e serial) Slaves. In this example the 805U-E Access Point is configured
with the “RS232 Modbus/TCP to RTU Gateway” enabled. Once enabled, the gateway
converts the Modbus/TCP queries received from the Master into Modbus RTU queries and
forwards these over the RS232 port to the Slave. When the serial response to the query
arrives from the Slave, it is converted to a Modbus/TCP response and forwarded via the
network to the Modbus/TCP Master. If no response was received serially by the 805U-E
within the configured Response Timeout, the 805U-E will initiate a number of retries
specified by the configured Maximum Request Retries.
The Modbus TCP to RTU Server may be configured to operate on either the RS-232 or
RS-485 port. It does not support operation on both ports at the same time.
Enable RS-232 Modbus
TCP to RTU Gateway
Check this box to enable the Modbus TCP to RTU Server on the RS-232
port. Only a single serial port is allowed at a time.
Enable RS-485 Modbus
TCP to RTU Gateway
Check this box to enable the Modbus TCP to RTU Server on the RS-485
port. Only a single serial port is allowed at a time.
Data Rate The serial data rate desired. Serial data rates available range from 110bps
to a maximum of 38,400bps.
Data Bits Parity Stop Bits The data format desired. Data formats of 8N1, 7E1, 7O1, 7E2, 7O2 are
supported.
Pause Between Requests Enter the delay between serial request retries in milliseconds
Response Timeout Enter the serial response timeout in milliseconds – a serial retry will be
sent if a response is not received within this timeout.
Connection Timeout Enter the TCP connection timeout in seconds – if no Modbus/TCP data
is received within this timeout then the TCP connection will be dropped.
Set this field to zero for no timeout.
Maximum Request Retries Enter the maximum number of request retries performed serially.
Maximum Connections Enter the maximum number of simultaneous TCP connections to the
server allowed.
Client
LAN
Modbus/TCP Client
(Master)
RS232
Modbus RTU
Slave
RS232
Modbus/TCP to
RTU Server
Access
Point